language IT | EN  face Welcome Guest | Login

UV Flame Detector
with embedded optical shutter for permanent use
monitoring hydrogen, gas, oil and combination burners

UV8 – Ultraviolet scanner – electro-optical shutter

• Compact unit for industrial use.
• Long life.
• High sensitivity.
• Blind to sunlight.
• Standard connector for quick replacement.
• Thermal insulating coupling.

DIMENSIONS
202 x 86 x 47.5 mm
WITH CONNECTOR
1 FEMALE CONNECTOR SIDE ENTRY
4 POLES + EARTH – PG11
2 MALE CONNECTOR WITH LEVER
4 POLES + EARTH
3 ALUMINIUM BODY
GRAY POLYESTER COATING
4 EPOXY GLASS INSULATOR
GRAY POLYESTER COATING
5 3⁄4” GAS BURNER HEAD CONNECTION
NICKEL PLATED BRASS

INTERNAL QUARTZ GLASS PROTECTION
TRANSMITTANCE > 92% @190 nm
WITH MINERAL FIBER SEALING GASKETS

OPTIONAL COOLING JOINT
EPOXY GLASS – GRAY POLYESTER COATING
5 1⁄4” COOLING AIR CONNECTION
WITH STAINLESS STEEL GRUB SCREWS

WEIGHT 75 g

DO NOT INSTALL ON TOP IN VERTICAL POSITION WHEN COMBUSTION PRODUCTS CAN FILL THE VOLUME IN FRONT OF THE SENSOR

ORDER CODE DESCRIPTION NOTE
1450.08.00 UV8
UV flame detector + electro optical shutter
ACTIVE
1450.OJ.00 UCJ
Cooling joint
ACTIVE
CKF04N – CONNECTOR
WIRE GAUGE 2 x 0,75 &hellip ;2,5 mm2
1 POSITIVE TERMINAL
CONNECT TO Q2 TERMINAL 09 or 11
2 NEGATIVE TERMINAL
CONNECT TO Q2 TERMINAL 10
3 SHUTTER SUPPLY
CONNECT TO Q2 TERMINAL S1
4 SHUTTER SUPPLY
CONNECT TO Q2 TERMINAL S2
Optical / Electrical
  • • Spectral Response185 … 260 nm
  • • UV Operating Voltage200 … 280 VAC
  • • Shutter Operating Voltage85 … 305 VAC
  • • Shutter Power Consumption< 3 W
  • • Shutter Pulse Time100 ms
  • • Sensitivity5000 cpm
  • • Operating Life> 20.000 hours @ 50°C
  • • Weight360 g
Environment
  • • Operating Temperature-40 … +125°C
  • • Vibration0.5 G MAX
  • • Relative Humidity10 … 90% 1
  • • Protection ClassIP65 / NEMA4
  • • Mounting Position ANY

1 NON CONDENSING

SPECTRAL RESPONSE